WEG Inverter Setup

Cette page contient des modifications qui ne sont pas marquées pour la traduction.

Auteur avatarStuga Engineer | Dernière modification 28/10/2024 par Gareth Green en cours de rédaction

How to set up the WEG inverters. used on the Transfer crank and Infeed modules.

History

Date Photo
2021 Original Unit fitted due to supply chain issues with Eaton Motor Starters
WEG Inverter Setup WEG INV.jpg
2024 IO Module added to allow a fault signal to be fed back to control system

see ECN004 WEG Inverter Update - Fault Output

...Additional parameters needed when using IO block

WEG Inverter with IO.png

Easy Start Guide

WEG Inverter Setup WEG.JPG

Parameters

Parameter Settings
Number Setting Function Notes
P100 Accel Time See Below
P101 Decel Time See Below
P133 50 Min Frequency Ref
P134 50 Max Frequency Ref
P271 1 Set DIx to 24v DC
P220 1 Remote Selection
P226 4 Remote Rotate Selection
P227 1 Remote Run Selection
P263 4 DI1 Function (FWD)
P264 5 DI2 Function (REV)
P265 20 DI3 Function (RESET) Only Used when IO Module is fitted to front of unit
P266 40 DI4 Function (ESTOP)
P275 13 DO1 Function (FAULT)


Accel and Decel (P100 & P101) Values
Machine Type Inverter Location

(Module Panel)

Motor Location

(Module)

Motor P100 P101
ZX5 A A Infeed Conveyor 0.1 0.1
A A Infeed Wheel 0.1 0.1
B C Crank 0.5 0.1
B D Crank 1.0 0.2
B E Crank 0.5 0.1
Autoflow Mk4 B A Infeed conveyor 0.5 0.5

Further Information

Programming Manual


Commentaires

P265 and P266
Gareth Green|Publié le Oct 25 at 11:08 am|
00

Matthew Preston Also reports on Z094 that P265 had to be set at 0 not 20 to work, Also P266 had to be set at 0 not 40 to work. These where the values in the 2 other units that where working

NOTE
Gareth Green|Publié le Oct 24 at 3:41 pm|
00

Please note : Z094 recently when fitting a new Unit that not all the Parameters above exist Like P275 - Unless it has that module fitted.

Published